Notifications
You must be signed in to change notification settings - Fork 6
Commit
This commit does not belong to any branch on this repository, and may belong to a fork outside of the repository.
Merge pull request #1240 from pnnl/RS/YJ/Rule_23-4
RS/YJ/Rule 23-4
- Loading branch information
Showing
4 changed files
with
497 additions
and
5 deletions.
There are no files selected for viewing
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,99 @@ | ||
from rct229.rule_engine.partial_rule_definition import PartialRuleDefinition | ||
from rct229.rule_engine.rule_list_indexed_base import RuleDefinitionListIndexedBase | ||
from rct229.rule_engine.ruleset_model_factory import produce_ruleset_model_instance | ||
from rct229.rulesets.ashrae9012019 import BASELINE_0, PROPOSED | ||
from rct229.rulesets.ashrae9012019.ruleset_functions.baseline_system_type_compare import ( | ||
baseline_system_type_compare, | ||
) | ||
from rct229.rulesets.ashrae9012019.ruleset_functions.baseline_systems.baseline_system_util import ( | ||
HVAC_SYS, | ||
) | ||
from rct229.rulesets.ashrae9012019.ruleset_functions.get_baseline_system_types import ( | ||
get_baseline_system_types, | ||
) | ||
from rct229.rulesets.ashrae9012019.ruleset_functions.get_lab_zone_hvac_systems import ( | ||
get_lab_zone_hvac_systems, | ||
) | ||
|
||
APPLICABLE_SYS_TYPES = [ | ||
HVAC_SYS.SYS_5, | ||
HVAC_SYS.SYS_7, | ||
] | ||
|
||
|
||
class Section23Rule4(RuleDefinitionListIndexedBase): | ||
"""Rule 4 of ASHRAE 90.1-2019 Appendix G Section 23 (Air-side)""" | ||
|
||
def __init__(self): | ||
super(Section23Rule4, self).__init__( | ||
rmrs_used=produce_ruleset_model_instance( | ||
USER=False, BASELINE_0=True, PROPOSED=True | ||
), | ||
each_rule=Section23Rule4.RuleSetModelInstanceRule(), | ||
index_rmr=BASELINE_0, | ||
id="23-4", | ||
description="Baseline systems 5 & 7 serving lab spaces per G3.1.1c shall reduce lab exhaust and makeup air during unoccupied periods to 50% of zone peak airflow, the minimum outdoor airflow, or rate required to comply with minimum accreditation standards whichever is larger.", | ||
ruleset_section_title="HVAC - Airside", | ||
standard_section="Exception to G3.1.3.13 VAV Minimum Flow Set Points (Systems 5 and 7)", | ||
is_primary_rule=False, | ||
list_path="ruleset_model_descriptions[0]", | ||
required_fields={ | ||
"$": ["calendar", "weather"], | ||
"weather": ["climate_zone"], | ||
"calendar": ["is_leap_year"], | ||
}, | ||
data_items={ | ||
"climate_zone_b": (BASELINE_0, "weather/climate_zone"), | ||
"is_leap_year_b": (BASELINE_0, "calendar/is_leap_year"), | ||
}, | ||
) | ||
|
||
class RuleSetModelInstanceRule(PartialRuleDefinition): | ||
def __init__(self): | ||
super(Section23Rule4.RuleSetModelInstanceRule, self).__init__( | ||
rmrs_used=produce_ruleset_model_instance( | ||
USER=False, BASELINE_0=True, PROPOSED=True | ||
), | ||
) | ||
|
||
def get_calc_vals(self, context, data=None): | ||
rmd_b = context.BASELINE_0 | ||
rmd_p = context.PROPOSED | ||
climate_zone_b = data["climate_zone_b"] | ||
is_leap_year_b = data["is_leap_year_b"] | ||
|
||
baseline_system_types_dict = get_baseline_system_types(rmd_b) | ||
|
||
hvac_sys_5_or_7_list = [ | ||
system_type | ||
for system_type in baseline_system_types_dict | ||
for applicable_sys_type in APPLICABLE_SYS_TYPES | ||
if baseline_system_type_compare( | ||
system_type, applicable_sys_type, False | ||
) | ||
] | ||
|
||
hvac_systems_serving_lab_zones = get_lab_zone_hvac_systems( | ||
rmd_b, rmd_p, climate_zone_b, is_leap_year_b | ||
) | ||
|
||
return { | ||
"hvac_sys_5_or_7_list": hvac_sys_5_or_7_list, | ||
"hvac_systems_serving_lab_zones": hvac_systems_serving_lab_zones, | ||
} | ||
|
||
def applicability_check(self, context, calc_vals, data): | ||
hvac_sys_5_or_7_list = calc_vals["hvac_sys_5_or_7_list"] | ||
hvac_systems_serving_lab_zones = calc_vals[ | ||
"hvac_systems_serving_lab_zones" | ||
] | ||
|
||
return any( | ||
[ | ||
hvac_sys_id | ||
for hvac_sys_id in hvac_systems_serving_lab_zones[ | ||
"lab_zones_only" | ||
] | ||
if hvac_sys_id in hvac_sys_5_or_7_list | ||
] | ||
) |
Oops, something went wrong.