Merge pull request #1240 from pnnl/RS/YJ/Rule_23-4
Browse files Browse the repository at this point in the history
RS/YJ/Rule 23-4
  • Loading branch information
weilixu authored Jan 16, 2024
2 parents 639e605 + 402a813 commit d58f916
Show file tree
Hide file tree
Showing 4 changed files with 497 additions and 5 deletions.
12 changes: 7 additions & 5 deletions docs/section23/Rule23-4.md
Original file line number Diff line number Diff line change
Expand Up @@ -5,15 +5,15 @@
**Mandatory Rule:** False
**Rule ID:** 23-4
**Rule Description:** Baseline systems 5 & 7 serving lab spaces per G3.1.1c shall reduce lab exhaust and makeup air during unoccupied periods to 50% of zone peak airflow, the minimum outdoor airflow, or rate required to comply with minimum accreditation standards whichever is larger.
**Rule Assertion:** B-RMR = expected value
**Rule Assertion:** B-RMD = expected value
**Appendix G Section:** Section 23 Air-side
**90.1 Section Reference:** Exception to G3.1.3.13 VAV Minimum Flow Set Points (Systems 5 and 7)
**Data Lookup:** None
**Evaluation Context:** Building

**Applicability Checks:**

1. B-RMR is modeled with at least one air-side system that is Type-5 or 7 and serves only lab spaces.
1. B-RMD is modeled with at least one air-side system that is Type-5 or 7 and serves only lab spaces.

**Function Calls:**

Expand All @@ -23,18 +23,20 @@

**Applicability Checks:**
- create a list of the target system types: `APPLICABLE_SYS_TYPES = [HVAC_SYS.SYS_5, HVAC_SYS.SYS_7]`
- Get B-RMR system types: `baseline_hvac_system_dict = get_baseline_system_types(B-RMR)`
- Get B-RMD system types: `baseline_hvac_system_dict = get_baseline_system_types(B-RMD)`
- Get climate zone: `climate_zone_b = ASHRAE229.weather.climate_zone`
- Get is_leap_year: `is_leap_year_b = ASHRAE229.calendar.is_leap_year`

- make a list of hvac system type ids for systems that are one of 5 or 7: `hvac_sys_5_or_7_list = []`
- loop through the applicable system types: `for target_sys_type in APPLICABLE_SYS_TYPES:`
- and loop through the baseline_system_types_dict to check the system types of the baseline systems: `for system_type in baseline_system_types_dict:`
- do baseline_system_type_compare to determine whether the baseline_system_type is the applicable_system_type: `if((baseline_system_type_compare(system_type, target_sys_type, false)):`
- the systems in the list: baseline_system_types_dict[system_type] are either sys-5 or 7, add them to hvac_sys_5_or_7_list: `hvac_sys_5_or_7_list.extend(baseline_system_types_dict[system_type])`
- use the function get_lab_zone_hvac_systems to get a list of systems serving lab zones: `hvac_systems_serving_lab_zones = get_lab_zone_hvac_systems(B-RMR)`
- use the function get_lab_zone_hvac_systems to get a list of systems serving lab zones: `hvac_systems_serving_lab_zones = get_lab_zone_hvac_systems(B-RMD, P-RMD, climate_zone, is_leap_year)`
- we'll iterate through the hvac systems serving labs. hvac_systems_serving_lab_zones has two keys - one indicating "LAB_ZONES_ONLY" and one indicating "LAB_AND_OTHER", because this rule references G3.1.1c, which requires systems to serve only lab zones, we will concern ourselves only with "LAB_ZONES_ONLY": `for hvac_system_id in hvac_systems_serving_lab_zones["LAB_ZONES_ONLY"]:`
- now check if this system is a System 5 or System 7 by looking for the hvac_system_id in hvac_sys_5_or_7_list, it is, the rule is applicable: `if(hvac_system_id in hvac_sys_5_or_7_list): UNDETERMINED`

- Else, rule is not applicable to B-RMR: `else: RULE_NOT_APPLICABLE`
- Else, rule is not applicable to B-RMD: `else: RULE_NOT_APPLICABLE`

**Notes:**

Expand Down
1 change: 1 addition & 0 deletions rct229/rulesets/ashrae9012019/section23/__init__.py
Original file line number Diff line number Diff line change
Expand Up @@ -5,6 +5,7 @@
"section23rule1",
"section23rule2",
"section23rule3",
"section23rule4",
"section23rule6",
"section23rule7",
"section23rule8",
Expand Down
99 changes: 99 additions & 0 deletions rct229/rulesets/ashrae9012019/section23/section23rule4.py
Original file line number Diff line number Diff line change
@@ -0,0 +1,99 @@
from rct229.rule_engine.partial_rule_definition import PartialRuleDefinition
from rct229.rule_engine.rule_list_indexed_base import RuleDefinitionListIndexedBase
from rct229.rule_engine.ruleset_model_factory import produce_ruleset_model_instance
from rct229.rulesets.ashrae9012019 import BASELINE_0, PROPOSED
from rct229.rulesets.ashrae9012019.ruleset_functions.baseline_system_type_compare import (
baseline_system_type_compare,
)
from rct229.rulesets.ashrae9012019.ruleset_functions.baseline_systems.baseline_system_util import (
HVAC_SYS,
)
from rct229.rulesets.ashrae9012019.ruleset_functions.get_baseline_system_types import (
get_baseline_system_types,
)
from rct229.rulesets.ashrae9012019.ruleset_functions.get_lab_zone_hvac_systems import (
get_lab_zone_hvac_systems,
)

APPLICABLE_SYS_TYPES = [
HVAC_SYS.SYS_5,
HVAC_SYS.SYS_7,
]


class Section23Rule4(RuleDefinitionListIndexedBase):
"""Rule 4 of ASHRAE 90.1-2019 Appendix G Section 23 (Air-side)"""

def __init__(self):
super(Section23Rule4, self).__init__(
rmrs_used=produce_ruleset_model_instance(
USER=False, BASELINE_0=True, PROPOSED=True
),
each_rule=Section23Rule4.RuleSetModelInstanceRule(),
index_rmr=BASELINE_0,
id="23-4",
description="Baseline systems 5 & 7 serving lab spaces per G3.1.1c shall reduce lab exhaust and makeup air during unoccupied periods to 50% of zone peak airflow, the minimum outdoor airflow, or rate required to comply with minimum accreditation standards whichever is larger.",
ruleset_section_title="HVAC - Airside",
standard_section="Exception to G3.1.3.13 VAV Minimum Flow Set Points (Systems 5 and 7)",
is_primary_rule=False,
list_path="ruleset_model_descriptions[0]",
required_fields={
"$": ["calendar", "weather"],
"weather": ["climate_zone"],
"calendar": ["is_leap_year"],
},
data_items={
"climate_zone_b": (BASELINE_0, "weather/climate_zone"),
"is_leap_year_b": (BASELINE_0, "calendar/is_leap_year"),
},
)

class RuleSetModelInstanceRule(PartialRuleDefinition):
def __init__(self):
super(Section23Rule4.RuleSetModelInstanceRule, self).__init__(
rmrs_used=produce_ruleset_model_instance(
USER=False, BASELINE_0=True, PROPOSED=True
),
)

def get_calc_vals(self, context, data=None):
rmd_b = context.BASELINE_0
rmd_p = context.PROPOSED
climate_zone_b = data["climate_zone_b"]
is_leap_year_b = data["is_leap_year_b"]

baseline_system_types_dict = get_baseline_system_types(rmd_b)

hvac_sys_5_or_7_list = [
system_type
for system_type in baseline_system_types_dict
for applicable_sys_type in APPLICABLE_SYS_TYPES
if baseline_system_type_compare(
system_type, applicable_sys_type, False
)
]

hvac_systems_serving_lab_zones = get_lab_zone_hvac_systems(
rmd_b, rmd_p, climate_zone_b, is_leap_year_b
)

return {
"hvac_sys_5_or_7_list": hvac_sys_5_or_7_list,
"hvac_systems_serving_lab_zones": hvac_systems_serving_lab_zones,
}

def applicability_check(self, context, calc_vals, data):
hvac_sys_5_or_7_list = calc_vals["hvac_sys_5_or_7_list"]
hvac_systems_serving_lab_zones = calc_vals[
"hvac_systems_serving_lab_zones"
]

return any(
[
hvac_sys_id
for hvac_sys_id in hvac_systems_serving_lab_zones[
"lab_zones_only"
]
if hvac_sys_id in hvac_sys_5_or_7_list
]
)
Loading

0 comments on commit d58f916