Merge pull request #1606 from pnnl/RS/WX/update_23-17
add section 23-17 new rule.
- Loading branch information
Showing
3 changed files
with
423 additions
and
0 deletions.
There are no files selected for viewing
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
|
@@ -18,6 +18,7 @@ | |
"section23rule14", | ||
"section23rule15", | ||
"section23rule16", | ||
"section23rule17", | ||
] | ||
|
||
|
||
|
115 changes: 115 additions & 0 deletions
115
rct229/rulesets/ashrae9012019/section23/section23rule17.py
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,115 @@ | ||
from rct229.rule_engine.rule_base import RuleDefinitionBase | ||
from rct229.rule_engine.rule_list_indexed_base import RuleDefinitionListIndexedBase | ||
from rct229.rule_engine.ruleset_model_factory import produce_ruleset_model_description | ||
from rct229.rulesets.ashrae9012019 import BASELINE_0 | ||
from rct229.rulesets.ashrae9012019.ruleset_functions.baseline_system_type_compare import ( | ||
baseline_system_type_compare, | ||
) | ||
from rct229.rulesets.ashrae9012019.ruleset_functions.baseline_systems.baseline_system_util import ( | ||
HVAC_SYS, | ||
) | ||
from rct229.rulesets.ashrae9012019.ruleset_functions.get_baseline_system_types import ( | ||
get_baseline_system_types, | ||
) | ||
from rct229.schema.config import ureg | ||
from rct229.utils.assertions import getattr_ | ||
from rct229.utils.pint_utils import CalcQ | ||
|
||
APPLICABLE_SYS_TYPES = [ | ||
HVAC_SYS.SYS_2, | ||
HVAC_SYS.SYS_4, | ||
] | ||
|
||
|
||
class Section23Rule17(RuleDefinitionListIndexedBase): | ||
"""Rule 17 of ASHRAE 90.1-2019 Appendix G Section 23 (Air-side)""" | ||
|
||
def __init__(self): | ||
super(Section23Rule17, self).__init__( | ||
rmds_used=produce_ruleset_model_description( | ||
USER=False, BASELINE_0=True, PROPOSED=False | ||
), | ||
each_rule=Section23Rule17.HVACRule(), | ||
index_rmd=BASELINE_0, | ||
id="23-17", | ||
description="System 2 and 4 - Electric air-source heat pumps shall shall be modeled to continue to operate while auxiliary heat is energized.", | ||
ruleset_section_title="HVAC - Airside", | ||
standard_section="G3.1.3.1 Heat Pumps (Systems 2 and 4)", | ||
is_primary_rule=True, | ||
rmd_context="ruleset_model_descriptions/0", | ||
list_path="$.buildings[*].building_segments[*].heating_ventilating_air_conditioning_systems[*]", | ||
) | ||
|
||
def is_applicable(self, context, data=None): | ||
rmd_b = context.BASELINE_0 | ||
baseline_system_types_dict = get_baseline_system_types(rmd_b) | ||
|
||
return any( | ||
[ | ||
baseline_system_types_dict[system_type] | ||
and baseline_system_type_compare( | ||
system_type, applicable_sys_type, False | ||
) | ||
for system_type in baseline_system_types_dict | ||
for applicable_sys_type in APPLICABLE_SYS_TYPES | ||
] | ||
) | ||
|
||
def create_data(self, context, data): | ||
rmd_b = context.BASELINE_0 | ||
baseline_system_types_dict = get_baseline_system_types(rmd_b) | ||
applicable_hvac_sys_ids = [ | ||
hvac_id | ||
for sys_type in baseline_system_types_dict | ||
for target_sys_type in APPLICABLE_SYS_TYPES | ||
if baseline_system_type_compare(sys_type, target_sys_type, False) | ||
for hvac_id in baseline_system_types_dict[sys_type] | ||
] | ||
|
||
return { | ||
"applicable_hvac_sys_ids": applicable_hvac_sys_ids, | ||
"baseline_system_types_dict": baseline_system_types_dict, | ||
} | ||
|
||
def list_filter(self, context_item, data): | ||
hvac_sys_b = context_item.BASELINE_0 | ||
applicable_hvac_sys_ids = data["applicable_hvac_sys_ids"] | ||
|
||
return hvac_sys_b["id"] in applicable_hvac_sys_ids | ||
|
||
class HVACRule(RuleDefinitionBase): | ||
def __init__(self): | ||
super(Section23Rule17.HVACRule, self).__init__( | ||
rmds_used=produce_ruleset_model_description( | ||
USER=False, BASELINE_0=True, PROPOSED=False | ||
), | ||
required_fields={ | ||
"$": ["heating_system"], | ||
}, | ||
precision={ | ||
"heatpump_low_shutoff_b": { | ||
"precision": 0.1, | ||
"unit": "K", | ||
}, | ||
}, | ||
) | ||
|
||
def get_calc_vals(self, context, data=None): | ||
hvac_b = context.BASELINE_0 | ||
baseline_system_types_dict = data["baseline_system_types_dict"] | ||
|
||
heating_system_b = hvac_b["heating_system"] | ||
heatpump_low_shutoff_b = getattr_( | ||
heating_system_b, "HeatingSystem", "heatpump_low_shutoff_temperature" | ||
) | ||
return { | ||
"heatpump_low_shutoff_temperature": CalcQ( | ||
"temperature", heatpump_low_shutoff_b | ||
), | ||
} | ||
|
||
def rule_check(self, context, calc_vals=None, data=None): | ||
heatpump_low_shutoff_b = calc_vals["heatpump_low_shutoff_temperature"] | ||
# The heat pump low shutoff temperature equal to the flag of -999, which indicates that there is no low-temperature shutoff for the heatpump | ||
# The minimum temperature is not finalized and is up for discussion. Must coordinate with the note provided in the schema element: HeatingSystem.heatpump_low_shutoff_temperature | ||
return heatpump_low_shutoff_b <= -999 * ureg("F") |