Skip to content

Commit

Permalink
include force_into_system as input to get_ashp_defaults
Browse files Browse the repository at this point in the history
  • Loading branch information
zolanaj committed Sep 25, 2024
1 parent 78b0429 commit f7534f1
Show file tree
Hide file tree
Showing 2 changed files with 20 additions and 35 deletions.
6 changes: 2 additions & 4 deletions data/ashp/ashp_defaults.json
Original file line number Diff line number Diff line change
Expand Up @@ -11,9 +11,8 @@
"can_serve_dhw": false,
"can_serve_space_heating": true,
"can_serve_cooling": true,
"force_into_system": false,
"back_up_temp_threshold_degF": 10.0,
"sizing_factor": 1.1,
"sizing_factor": 1.0,
"heating_cop_reference": [1.5,2.3,3.3,4.5],
"heating_cf_reference": [0.38,0.64,1.0,1.4],
"heating_reference_temps_degF": [-5,17,47,80],
Expand All @@ -33,9 +32,8 @@
"can_serve_dhw": true,
"can_serve_space_heating": false,
"can_serve_cooling": false,
"force_into_system": false,
"back_up_temp_threshold_degF": 10.0,
"sizing_factor": 1.1,
"sizing_factor": 1.0,
"heating_cop_reference": [1.5,2.3,3.3,4.5],
"heating_cf_reference": [0.38,0.64,1.0,1.4],
"heating_reference_temps_degF": [-5,17,47,80]
Expand Down
49 changes: 18 additions & 31 deletions src/core/ashp.jl
Original file line number Diff line number Diff line change
Expand Up @@ -68,7 +68,7 @@ function ASHPSpaceHeater(;
macrs_option_years::Int = 0, # MACRS schedule for financial analysis. Set to zero to disable
macrs_bonus_fraction::Real = 0.0, # Fraction of upfront project costs to depreciate under MACRS
can_serve_cooling::Union{Bool, Nothing} = nothing # If ASHP can supply heat to the cooling load
force_into_system::Union{Bool, Nothing} = nothing # force into system to serve all space heating loads if true
force_into_system::Bool = false # force into system to serve all space heating loads if true
avoided_capex_by_ashp_present_value::Real = 0.0 # avoided capital expenditure due to presence of ASHP system vs. defaults heating and cooling techs
#The following inputs are used to create the attributes heating_cop and heating cf:
Expand Down Expand Up @@ -101,7 +101,7 @@ function ASHPSpaceHeater(;
macrs_bonus_fraction::Real = 0.0,
avoided_capex_by_ashp_present_value::Real = 0.0,
can_serve_cooling::Union{Bool, Nothing} = nothing,
force_into_system::Union{Bool, Nothing} = nothing,
force_into_system::Bool = false,
heating_cop_reference::Array{<:Real,1} = Real[],
heating_cf_reference::Array{<:Real,1} = Real[],
heating_reference_temps_degF::Array{<:Real,1} = Real[],
Expand All @@ -114,18 +114,14 @@ function ASHPSpaceHeater(;
cooling_load::Array{<:Real,1} = Real[]
)

defaults = get_ashp_defaults("SpaceHeating")
defaults = get_ashp_defaults("SpaceHeating",force_into_system)

# populate defaults as needed
if isnothing(installed_cost_per_ton)
installed_cost_per_ton = defaults["installed_cost_per_ton"]
end
if isnothing(om_cost_per_ton)
if force_into_system == true
om_cost_per_ton = 0
else
om_cost_per_ton = defaults["om_cost_per_ton"]
end
om_cost_per_ton = defaults["om_cost_per_ton"]
end
if isnothing(can_serve_cooling)
can_serve_cooling = defaults["can_serve_cooling"]
Expand All @@ -140,11 +136,7 @@ function ASHPSpaceHeater(;
max_ton = defaults["max_ton"]
end
if isnothing(sizing_factor)
if force_into_system == true
sizing_factor = defaults["sizing_factor"]
else
sizing_factor = 1
end
sizing_factor = defaults["sizing_factor"]
end

if length(heating_cop_reference) != length(heating_cf_reference) || length(heating_cf_reference) != length(heating_reference_temps_degF)
Expand Down Expand Up @@ -264,7 +256,7 @@ function ASHPWaterHeater(;
macrs_bonus_fraction::Real = 0.0, # Fraction of upfront project costs to depreciate under MACRS
can_supply_steam_turbine::Union{Bool, nothing} = nothing # If the boiler can supply steam to the steam turbine for electric production
avoided_capex_by_ashp_present_value::Real = 0.0 # avoided capital expenditure due to presence of ASHP system vs. defaults heating and cooling techs
force_into_system::Union{Bool, Nothing} = nothing # force into system to serve all hot water loads if true
force_into_system::Bool = false # force into system to serve all hot water loads if true
#The following inputs are used to create the attributes heating_cop and heating cf:
heating_cop_reference::Array{<:Real,1}, # COP of the heating (i.e., thermal produced / electricity consumed)
Expand All @@ -289,7 +281,7 @@ function ASHPWaterHeater(;
macrs_option_years::Int = 0,
macrs_bonus_fraction::Real = 0.0,
avoided_capex_by_ashp_present_value::Real = 0.0,
force_into_system::Union{Bool, Nothing} = nothing,
force_into_system::Bool = false,
heating_cop_reference::Array{<:Real,1} = Real[],
heating_cf_reference::Array{<:Real,1} = Real[],
heating_reference_temps_degF::Array{<:Real,1} = Real[],
Expand All @@ -298,21 +290,14 @@ function ASHPWaterHeater(;
heating_load::Array{<:Real,1} = Real[]
)

defaults = get_ashp_defaults("DomesticHotWater")
defaults = get_ashp_defaults("DomesticHotWater",force_into_system)

# populate defaults as needed
if isnothing(installed_cost_per_ton)
installed_cost_per_ton = defaults["installed_cost_per_ton"]
end
if isnothing(om_cost_per_ton)
if force_into_system == true
om_cost_per_ton = 0
else
om_cost_per_ton = defaults["om_cost_per_ton"]
end
end
if isnothing(force_into_system)
force_into_system = defaults["force_into_system"]
om_cost_per_ton = defaults["om_cost_per_ton"]
end
if isnothing(back_up_temp_threshold_degF)
back_up_temp_threshold_degF = defaults["back_up_temp_threshold_degF"]
Expand All @@ -321,11 +306,7 @@ function ASHPWaterHeater(;
max_ton = defaults["max_ton"]
end
if isnothing(sizing_factor)
if force_into_system == true
sizing_factor = defaults["sizing_factor"]
else
sizing_factor = 1
end
sizing_factor = defaults["sizing_factor"]
end

if length(heating_cop_reference) != length(heating_cf_reference) || length(heating_cf_reference) != length(heating_reference_temps_degF)
Expand Down Expand Up @@ -410,16 +391,22 @@ Obtains defaults for the ASHP from a JSON data file.
inputs
load_served::String -- identifier of heating load served by AHSP system
force_into_system::Bool -- exclusively serves compatible thermal loads if true (i.e., replaces existing technologies)
returns
ashp_defaults::Dict -- Dictionary containing defaults for ASHP
"""
function get_ashp_defaults(load_served::String="SpaceHeating")
function get_ashp_defaults(load_served::String="SpaceHeating", force_into_system::Bool=false)
if !(load_served in ["SpaceHeating", "DomesticHotWater"])
throw(@error("Invalid inputs: argument `load_served` to function get_ashp_defaults() must be a String in the set ['SpaceHeating', 'DomesticHotWater']."))
end
all_ashp_defaults = JSON.parsefile(joinpath(dirname(@__FILE__), "..", "..", "data", "ashp", "ashp_defaults.json"))
return all_ashp_defaults[load_served]
defaults = all_ashp_defaults[load_served]
if force_into_system
defaults["sizing_factor"] = 1.1
defaults["om_cost_per_ton"] = 0.0
end
return defaults
end

"""
Expand Down