Vista to SBO Conversion Tools

Modbus slave transition

Converts Vista Modbus slave registers to SBO Modbus Interface registers.

NOTE: Currently only supports Digital Coil register types.

Image of imported Modbus Interface System Tree

Directions:

There are some manual steps that must first be taken in Vista.

  • In Vista Workstation, edit the Xenta Server hosting the Modbus Slave.

Image of imported Modbus Interface System Tree

  • The XBuilder project opens. Navigate to the Modbus Slave object, Edit Device Template.

Image of XBuilder

  • The XBuilder Device Editor opens. In the data table, select the top-left cell to select all rows. Copy.

Image of XBuilder Device Editor

  • In an Excel workbook, paste the data. For mulitple Modbus Slaves, repeat steps, pasting into a either a new sheet in the same workbook or append to the list in the same sheet.

Image of Excel

  • Save the workbook.

  • Clone this repository. Example usage for generating the XML for importing into SBO is provided below.

# This is a very long and ugly import call. I should probably clean it up one day
from SmartStruxure-engineering-toolkit.legacy_system.vista.modbus_slave_transition import ModbusSlaveTransition

# The Excel workbook you just created
my_xlfile = 'Example Modbus register schedule.xlsx'

# The XML filename you want to output to for importing into SBO
my_xmlfile = 'Example SBO Modbus registers output.xml'

# instantiate ModbusSlaveTransition object
sbo_modbus_converter = ModbusSlaveTransition(xlfile=my_xlfile, xmlfile=my_xmlfile)

# create SBO xml for importing
sbo_modbus_converter.make_xml()
  • If successful, the XML file can be imported into a SmartStruxure Server.

Image of imported Modbus Interface System Tree